Model Number |
ZSF |
Applications
Applicable Loads Computer, OA equipments, Electronic fluorescent lamp, Single Phase SCR heater and UPS etc. Applicable System Single phase nonlinear loads on Three phase four wire system Applicable Locations Office/Commercial building, School, Shopping Mall, Department store, Apartment, Hospital, Factory etc.
Benefits
Reduce Line Current The ZSF can reduce rms value of line current by reducing zero sequence harmonic current that is produced by single phase non-linear loads in three phase four wire system. Reduce Neutral Current The zero sequence current in line make a large neutral harmonic current by trebling. The ZSF can reduce this large neutral current up to 90% depend on ZSF location. Meet IEEE Std.519-1992 The ZSF enable most single phase non-linear loads to comply with both the voltage and current distortion limits of IEEE Std.519-1992 and other international limits such as AS-2279, EN61000-3-4, and BS G5/4.
Solve Power Quality Problems
- Protect loss and reduce capacity because of circulating effects by zero sequence harmonic current in transformer.
- Protect heating and loss of line and neutral cable that is effected by zero sequence harmonic current.
- Reduce unbalance of line current.
- Improve power factor.
- Reduce system loss.
- Reduce K-factor rating of load current at main transformer.
Economical and stand-alone solution The ZSF is standardized up to 3000A. Therefore, if maximum neutral current can be figure out, the site survey and system simulation before installing are not necessary.
Features & Options
Compact and easy-to-install. Quite operation and proper ventilation. Neutral size for three times of line current. Standardized up to 3000A (based on neutral current). Ammeter displaying the neutral current in option. Neutral impedance adjuster upon request.
Principles
Duplicating Principle of zero sequence harmonic The zero sequence harmonic current produced by single phase non-linear loads can treble in neutral line and make problems.
Removing principle of zero sequence harmonic Up to 90% maximum of zero sequence harmonic current flow into zero sequence transformer in the ZSF because zero sequence transformer is specially designed to have very low zero sequence impedance. This can effectively be moved zero sequence harmonic currents upstream from the ZSF.
Selection Tables Select Zero sequence Filters based on the maximum neutral current at the location that ZSF will be installed.
|
Catalog Number
|
Currents in neutral [A]
|
DIMENSIONS [mm]
|
WEIGHT [kg]
|
DRAWING
|
|
W
|
D
|
H
|
|
ZSF22030
|
30
|
350
|
500
|
500
|
70
|
Fig A
|
|
ZSF22060
|
60
|
350
|
500
|
500
|
85
|
Fig A
|
|
ZSF22100
|
100
|
600
|
400
|
850
|
150
|
Fig A
|
|
ZSF22150
|
150
|
650
|
450
|
900
|
180
|
Fig A
|
|
ZSF22300
|
300
|
800
|
450
|
1000
|
350
|
Fig B
|
|
ZSF22450
|
450
|
800
|
500
|
1200
|
400
|
Fig B
|
|
ZSF22600
|
600
|
800
|
1500
|
2350
|
800
|
Fig B
|
|
ZSF221000
|
1000
|
1100
|
1500
|
2350
|
1500
|
Fig B
|
|
ZSF223000
|
3000
|
1100
|
1500
|
2350
|
3000
|
Fig B
|
Table 1. Selection table of the ZSF
- Current = Maximum neutral current
- W = Width, D = Depth, H = Height
- All weight and dimensions are subject to change without notice. Recommended Ratings = Ip 3 (Ip = Phase currents in rms)

Step1. Find proper location Find proper location where the ZSF can be installed. Reduction ratio can be maximized if the ZSF is installed as close as possible to load side. Step2. Measure max current at neutral line Measuring max current at neutral line is very important to choose the rating of ZSF. If the rating of ZSF should be decided without measured current or design process, three times of max current at phase can be considered as max current at neutral line. Step3. Choose the rating of ZSF at Table 1 Choose the proper rating of ZSF at Table 1 with max current at neutral line.
G. Case studies of the ZSF Case 1. Apartment - Installed Product: ZSF22600 [600A] - Problem: an electricity failure by a large amount of neutral current produced by non-linear loads

Installing result: 75% reduction of neutral current

Case 2. Governmentt - Installed Product: ZSF2260 x 5 [60A] - Problem: an electricity failure by computer, OA equipment, and other single-phase non-linear loads - Installing result: 84% reduction of neutral current
|
Installation Placee
|
Product
|
Neural Current
|
Reduction (%)
|
|
|
ZSF 22060
|
422
|
7
|
83.3
|
|
1/2 Floor
|
98
|
23
|
76.5
|
|
3/4 Floor
|
67
|
17
|
74.6
|
|
5/6 Floor
|
57
|
14
|
75.4
|
|
7/8 Floor
|
46
|
12
|
73.9
|


|